Abstract

Seeing the harmful effects of the magnetic field on human health, the task of reducing the magnetic flux density in places of people long-term stays near power lines is actual. One of the ways to solve this problem is a passive shielding. Analyze of shielding efficiency was performed by computer simulation using COMSOL Multiphysics software. It was created a 2D model of a three-phase 330 kV overhead power transmission line and the research area, which is a conventional residential building located outside the security zone. The magnetic field was simulated and the value of magnetic flux density in the research area was determined for cases of using a passive grid electromagnetic screen of different configurations. The efficiency comparison of different shields was performed qualitatively on the color and contour maps of the magnetic flux density distribution in the research area and quantitatively on the average value of the shielding factor. The efficiency of a single layer vertical shield, located on the building wall closest to the power line, and a horizontal shield, located at the average height of the building, were compared. It is shown that with the same metal content (the same diameter of the shield conductors and the same number of them) the vertical shield is more efficient than the horizontal, but it also cannot always provide a safe level of magnetic flux density. The configuration of the multilayer shield, which can be placed in overlapping between floors of the building, is presented. It is shown that with the same metal content such shield can provide better reducing of the magnetic field than a single-layer, and it is able, under the same conditions, to decrease the magnetic flux density to a safe level. But this configuration has one disadvantage. In the part of the building closer to the power line (approximately 4 m from the wall) the value of magnetic flux density exceeds the safe level. It is possible to reduce the width of such zone due to a denser placement of shield conductors. It was also found that the placement of the shield horizontal layers on each floor is more effective, i.e. as evenly as possible over the research area. In addition, a research the dependence of the shielding factor of the multilayer shield on the conductor’s diameter and the distance between them. It is shown that such shield allows reducing the average value of magnetic flux density in the research area hundreds of times, although with a fairly large metal content.

Keywords

References

  1. A. Giorgi, R. Conti, R. Rendina, L. Sartore and E. Sena, "Technical Solutions To Reduce 50 Hz Magnetic Fields from Power Lines," in Proceedings of Power Tech Conference IEEE’2003, 23-26 June, 2003, Bologna (Italy), 2003.
  2. M. Feychting, B. Floderus and A. Ahlbom, "Parental occupational exposure to magnetic fields and childhood," Cancer Causes and Control, vol. 11, no. 2, pp. 151-156, 2000.
  3. V. Yu. Rozov, S. Yu. Reutskiy, D. Ye. Pelevin, O. Yu. Pyliugina, "Magnitnoe pole linij elektroperedachi i metody ego snizheniya do bezopasnogo urovnya [The magnetic field of power transmission lines and the methods of its mitigation to a safe level]," Tekhnichna elektrodynamika, no. 2, pp. 3-9, 2013. URL: http://techned.org.ua/2012_2/st8.pdf
  4. D. Ye. Pelevin, "Ekranirovanie magnitnogo polya promyshlennoj chastoty stenami zhilyh domov [Screening magnetic fields of the power frequency by the walls of houses]," Elektrotekhnika i Elektromekhanika, no. 4, pp. 53-55, 2015. DOI: 10.20998/2074-272X.2015.4.10
  5. A. O. Pavlushko, A. V. Dymerets, A. V. Krasnozhon, "Matematychne modeliuvannia parametriv elektromahnitnoho polia diiuchoi PL 330 kV [Mathematical modeling of electromagnetic field parameters of the overhead power line 330 kV]," in Vseukrainska naukovo-praktychna konferentsiia «Novitni Tekhnolohii Suchasnoho Suspilstva» NTSS-2019, Chernihiv, Ukraine, 2019.
  6. M. Sh. Misrihanov, A. Yu. Tokarskiy, "Preimushestva i nedostatki prostyh kompaktnyh vozdushnyh linij elektroperedachi [Advantages and disadvantages simple compact overhead power lines]," Povyshenie effektivnosti raboty energosistem, pp. 204-223, 2003.
  7. M. Sh. Misrihanov, A. Yu. Tokarskiy, "Upravlyaemye kompaktnye linii elektroperedachi [Managed compact power lines]," Trudy IGEU, no. 6, pp. 238-248, 2003.
  8. S. Celozzi, F. Garzia, "Active shielding for power-frequency magnetic field reduction using genetic algorithms optimization," IEE Proceedings – Science, Measurement and Technology, vol. 151, no. 1, pp. 2-7, 2004.
  9. B. I. Kuznetsov, T. B. Nikitina, A. V. Voloshko, I. V. Bovdyj, E. V. Vinichenko, B. B. Kobilyanskiy, "Sintez sistem aktivnogo ekranirovaniya magnitnogo polya vozdushnyh linij elektroperedachi na osnove mnogokriterialnoj optimizacii [Synthesis of an active shielding system of the magnetic field of power lines based on multiobjective optimization]," Elektrotekhnika i Elektromekhanika, no. 6, pp. 26-30, 2016. DOI: 10.20998/2074-272X.2016.6.05
  10. J. Burnett, P. Du Yaping, "Mitigation of extremely low frequency magnetic fields from electrical installations in high-rise buildings,". Building and Environment, vol. 37, no 8-9. pp. 769-775, 2002. DOI: 10.1016/S0360-1323(02)00043-4 .
  11. M. De Wulf, P. Wouters, P. Sergeant, L. Dupreґ, E. Hoferlin, S. Jacobs, P. Harlet, "Electromagnetic shielding of high-voltage cables," Journal of Magnetism and Magnetic Materials, no 316, pp. 908-911, 2007. DOI: 10.1016/j.jmmm.2007.03.137
  12. M. M. Rezinkina, V. S. Grinchenko, " Elektromagnitnye ekrany dlya snizheniya indukcii magnitnogo polya promyshlennoj chastoty na obektah energetiki [Usage of electromagnetic shields for power frequency magnetic field mitigation in power industry]," Tekhnichna elektrodynamika, no. 3, pp. 15-16, 2012. URL: http://techned.org.ua/2012_3/st5.pdf
  13. D. Bavastro, A. Canova, F. Freschi, L. Giaccone, M. Manca, "Magnetic field mitigation at power frequency: design principles and case studies," IEEE Transactions on Industry Applications, vol. 51, no 3, pp. 2009-2016, 2015. DOI: 10.1109/TIA.2014.2369813
  14. A. Canova, D. Bavastro, F. Freschi, L. Giaccone, M. Repetto "Magnetic shielding solutions for the junction zone of high voltage underground power lines," Electric Power Systems Research, no 89. pp. 109-115, 2012. DOI: 10.1016/j.epsr.2012.03.003
  15. P. L. Cruz Romero, J. C. Del-Pino-Lуpez, "Magnetic field shielding of underground cable duct banks," Progress In Electromagnetics Research, no 138, pp. 1-19, 2013.
  16. М. М. Rezinkina, А.А. Shcherba, V.S. Grinchenko, K.O. Rezinkina, "Raschetnyj vybor parametrov elektromagnitnyh ekranov slozhnoj prostranstvennoj konfiguracii [Calculation choice of parameters of electromagnetic screens of complicated three-dimensional configuration]," Tekhnichna elektrodynamika, no. 1, pp. 10-16, 2012. URL: http://techned.org.ua/2012_1/st2.pdf
  17. E. Salinas, M. Rezinkina, J. Atalaya, "Some 2D–3D aspects of shielding of longitudinal sources of extremely low frequency magnetic fields," The Environmentalist, vol. 29, no 2, pp. 141-146, 2009. DOI: 10.1007/s10669-008-9206-0 .
  18. V. S. Grinchenko, "Znyzhennya mahnitnoho polya tryfaznykh liniy elektroperedachi hratchastym elektromahnitnym ekranom [Mitigation of three-phase power line magnetic field by grid electromagnetic shield]," Tekhnichna elektrodynamika, no. 4, pp. 29-32, 2018. DOI: 10.15407/techned2018.04.029
  19. D. N. Shapiro, Basis of electromagnetic screening, Leningrad: Energiia, 1975, 109 p.
§ 06 — Related

Similar articles in this journal

Related peer-reviewed studies published in this journal.
View all issues

Mechanicaly Reconfigurable Antenna with Ionic-Polymer Metal Composite

Artem Serhiyovych Chernov, Oleksii O. Malyshok, Victor Anatoliiovych Kazmirenko, Irina Petrivna Holubeva, Yuriy Vasylovych Prokopenko, Guy A. E. Vandenbosch

This paper presents the possibility of employing an ionic polymer–metal composite (IPMC) actuator for coplanar waveguide fed antenna reconfiguration. Proposed antenna…

#defected ground structure #filtenna #frequency tuning #IMPC actuator
p. 343504.1-343504.6
10.20535/2523-4455.mea.343504

Interaction of Silver Nanoparticles with a Substrate Under Plasmonic Resonance Conditions

Yurii I. Mysiuk, Yurii B. Smachylo, Oleksandr V. Ilin, Tetiana Oleksandrivna Bulavinets, Iryna Y. Yaremchuk

The interaction between metal nanoparticles and substrates under plasmonic resonance conditions plays a crucial role in various optical applications. In this study, we…

#silver nanoparticles #extinction cross section #substrate #localized surface plasmon resonance
p. 303929.1-303929.6
10.20535/2523-4455.mea.303929

Similar Articles

1-10 of 82

You may also start an advanced similarity search for this article.